← Back to guides

How to Select EN 14511 Test Conditions for Commercial HPWH Modelling (VEU and ESS)

Alastair McDowell · Last reviewed 12 November 2026

Applies to
  • ESC Commercial and Industrial Air Source Heat Pump Water Heater Product Application Guide V2.1
  • IPART Water Heater Product Acceptance Guide (IHEAB) V1.2
  • AS/NZS 4234:2021
  • EN 14511:2022
On this page
  1. Minimum test conditions
  2. Maximum entering water temperature
  3. Water flow rate
  4. Extra test points that improve the map
  5. Starting matrix
  6. Common issues
  7. How EnergyAE can help
  8. Sources

VEU Activity 44 and the NSW ESS IHEAB method model a commercial heat pump water heater from its EN 14511 results. The TRNSYS model draws straight lines between map points and holds the edge value beyond them, so the conditions you book decide how accurate the model is.

Both schemes require at least one water temperature at or above the maximum in normal operation, tested at three air conditions: 7°C/6°C, 2°C/1°C, and either 12°C/11°C or 18 to 20°C. There is no need to test at -5°C.

EnergyAE also tests up to the highest entering water temperature the model will reach, uses the product’s own water flow control, and adds a 10°C point, a point near 50°C and a hot air point.

Commercial air-source heat pump in a laboratory test room, with flexible ducting and sampling stands around the unit.
A commercial air-source heat pump set up in a laboratory test room. Each condition tested becomes one point on the performance map the model uses.

Minimum test conditions

The ESC Product Application Guide V2.1 (VEU) and the IPART IHEAB Product Acceptance Guide V1.2 (ESS) set the same minimum.

ConditionRequirement
WaterAt least one water temperature at or above the maximum required during normal operation
Air 17°C dry bulb, 6°C wet bulb (EN 14511 standard rating condition)
Air 22°C/1°C. For a Class B product, the lowest air condition at which it can operate
Air 312°C/11°C, or 18 to 20°C with a dew point of 11 to 14°C (19°C/15°C qualifies)

The ESC guide also requires enough points to represent the heat pump over its whole operating range. In EnergyAE’s experience, one water temperature at three air points rarely meets that.

Variable speed units also need EN 14825 testing or the default adjustments in AS/NZS 4234:2021. Ask the laboratory to report standby power. Reports must come from a NATA-accredited or equivalent laboratory.

There is no need to test at -5°C. The map is extended to the lowest air temperature in the weather files (-5°C in the ESC example) by straight-line extrapolation from the 7°C and 2°C results. The 2°C test therefore sets the slope for every colder hour.

Maximum entering water temperature

Test with an entering water temperature high enough that the model never needs a hotter one. Above the highest tested water temperature, the map holds the edge value and credits hotter water with the better performance of cooler water.

EnergyAE works backwards from the tank set point:

  1. Start from the set point at the tank sensor, for example 70°C at mid-tank.
  2. Estimate what the heat pump must deliver to the top of the tank, for example 72 to 75°C.
  3. Subtract the temperature rise. With a 5 K rise, entering water reaches at most about 70°C.
  4. Test up to that temperature, here 70°C.

A controller cut-out can set the limit instead. A CO2 unit that stops when entering water exceeds 50°C needs testing only up to 50°C. Take the set point, rise and cut-out from the control declaration.

Water flow rate

The laboratory must control water flow the same way the real unit does, because the model must use the product’s actual control strategy.

Flow controlHow the laboratory runs each conditionTypical products
Fixed flow rateRated flow at every condition. Outlet temperature variesFixed or stepped pump speed
Fixed temperature riseFlow adjusted to hold the rise, for example 5 K: 10/15°C, 50/55°C, 70/75°CMost R-290 units EnergyAE sees (5 to 10 K rise)
Fixed outlet temperatureFlow adjusted to reach the set outlet in one passCO2 heat pumps

Read the flow control from the controller and pump specification, and give it to the laboratory with the test conditions.

Extra test points that improve the map

  • 10°C entering water, to record the high capacity and COP after a large draw-off.
  • An intermediate entering water temperature near 50°C, because capacity rarely changes in a straight line between the coldest and hottest points.
  • A hot air point of 30°C to 38°C. Without it, every warmer hour uses the values at the hottest tested air temperature.
0 5 10 15 20 10 30 50 70 Entering water temperature (°C) Heating capacity (kW) 19°C air 2°C air 7°C air 14.5 kW measured 8.6 kW without the 50°C test
At 7°C air, this R-290 unit delivered 14.5 kW with 50°C entering water. Without that test point, the map's straight line from 10°C to 70°C gives 8.6 kW, which is 40% low.

On the same unit at 50°C entering water, COP rose from 3.6 at 19°C air to 4.5 at 30°C air. Without the 30°C test, the model would use 3.6 for every warmer hour. Choose the hot point inside the declared operating range.

Starting matrix

These are EnergyAE’s starting points. Adjust them to the compressor envelope, controls and outlet temperature.

RefrigerantEntering water (°C)Air, dry bulb/wet bulb (°C)Tested points
R-29010, 50, 702/1, 7/6, 19/15, 38/2512
CO210, 30, 502/1, 7/6, 19/15, 38/2512
Air temperature, dry bulb/wet bulb (°C) Entering water (°C) -5 calculated 2/1 7/6 19/15 or 12/11 38/25 30 to 38 70 maximum inlet 50 intermediate 10 low Regulator minimum Recommended addition Extrapolated from 2°C and 7°C, not tested
For an R-290 unit with a 70°C maximum entering water temperature, three tests meet the minimum conditions in both guides, nine more give the map its shape, and the -5°C row is calculated from the 2°C and 7°C results.

Common issues

ProblemFix
An existing report stops below the maximum entering water temperatureSend it for review before assuming it can be used
An Ecodesign (ErP) report to EN 14825 is supplied as the EN 14511 reportCheck the test specification. A part-load ErP report cannot build the map
The laboratory says some conditions cannot be reachedIt applied a fixed outlet temperature to a unit that heats with a fixed rise. State the flow control with the conditions
Model numbers do not matchConfirm the final model number before the report is issued

How EnergyAE can help

Send us the refrigerant, control logic and declared operating range before you book the laboratory. EnergyAE will set the test matrix, review the results and complete the AS/NZS 4234 modelling for VEU and ESS.

Get in touch with EnergyAE to plan your test matrix.

Sources

  • Essential Services Commission, Commercial and Industrial Air Source Heat Pump Water Heater Product Application Guide (C/21/35298), V2.1, 24 July 2025. Checked 11 November 2026.
  • IPART, Guide: Water Heater Product Acceptance, IHEAB, V1.2, 12 March 2026. Checked 11 November 2026.
  • AS/NZS 4234:2021, Heated water systems: Calculation of energy consumption.
  • EN 14511-2:2022 and EN 14511-3:2022 test report for an R-290 commercial heat pump, tested July 2026 (product not named).