EnergyAE / Knowledge Base

Standards Reading List

Key clauses from relevant standards for HPWH modelling and scheme compliance.

Familiarize yourself with these essential sections from the key standards.

AS/NZS 5125.1:2014 — Heat Pump Water Heater Performance Testing

  • Section 2.2 — Test chamber conditions (test conditions 1–4)
  • Section 3.2 — Test conditions and maximum temperature requirements
  • Section 4.5 — Data correlation equations: selection of Tw (average tank) vs. Twi (inlet)
  • Section 5.2 — Low temperature classification (Class A, Class B)
  • Section 5.3 — Low temperature performance test and frosting penalty calculation
  • Appendix B — Regression methodology

AS/NZS 4234:2021 — Annual Energy Performance Calculation

System Design

  • Section 2.2.3 — Air-source heat pump systems
  • Section 2.3 — Storage tank types

Compliance

  • Section 3.6.2 — Legionella control strategies
  • Section 3.6.3 — Minimum delivery temperature (MDT) requirements

Modelling

  • Section 4.2 — Thermal stratification and mixing in hot water storage tanks
  • Section 4.3 — Modelling thermal stratification in storage tanks
  • Section 4.8 — Modelling heat pump water heaters:
    • Flow control for separate (stand-alone) heat pumps
    • Integral heat pump model setup
    • DTHX calibration
    • Stand-alone heat pump model setup
    • Variable flow modelling
    • Low temperature operation penalty calculation (frosting penalty)
  • Section 7.3 — Annual energy savings calculation relative to reference systems

Reference Data

  • Appendix A:
    • Climate zone weather data
    • Hot water demand loads (daily and seasonal profiles)
    • Cold water inlet temperature
    • Displaced energy calculation (STC)

AS/NZS 3498:2009 — Legionella Control

Section 7.1(j) defines two main legionella control methods. Choose based on test results and client preference.

Option 1: Weekly 90% Boost to 60°C + Daily Lower Setpoint

Requirements:

  • AS/NZS 5125.1 test data must show bottom sensor (T6) reaching ≥ 60°C at test end
  • HP must heat the entire tank to 60°C in one cycle
  • Identify the mid-tank temperature (T3) when T6 = 60°C — typically 61–63°C
  • Use this mid-tank temperature as the weekly setpoint

Typical settings:

  • Daily: 55°C / 5 K deadband
  • Weekly: 61°C / 1 K deadband (or based on observed T3)
  • Weekly boost: Monday ~2am–7am (once per week)

Notes: More efficient than daily-only methods, but requires careful calibration. Risk: if T3 falls short of 60°C, system does not meet compliance.

Option 2: Daily 45% Boost to 60°C (Safer Default)

Requirements:

  • HP sensor must have ≥ 45% tank volume above it
  • Setpoint: 60°C (fixed)
  • Maximize deadband while ensuring minimum delivery temperature ≥ 45°C

Typical settings:

  • Daily: 60°C / 10 K deadband

Notes: Simpler and safer. Less efficient than weekly/daily combined, but more forgiving of model variations.

Decision Framework

Use Option 2 (45% daily) when: In doubt, or for conservative approach. Safer compliance margin.

Use Option 1 (weekly + daily) when: Client prefers efficiency and test data clearly supports higher stratification. Requires full validation against test results.

Consult with the client on their preference balancing efficiency and compliance risk.